Cummins NTA855-G1A Diesel Generator Sets 220KW Specifications
Generator Set Technical Specification:
– Generator Set Model: HY-G200
– Prime Power(kW/kVA): 220kW/270kVA
– Standby Power(kW/kVA): 250kW/312.5kVA
– Output Voltage: 400/230V
– Frequency: 50Hz
– Rated Current: 369A
– Rated Speed(RPM): 1500
– Power Factor: COSΦ=0.8(lagging)
– Fuel Consumption: 206 L/hr
– Battery Rated Capacity(AH): 150AH 2PCS
– Gross Weight: 2900
– Overall Dimension (L*W*H)mm: 3000×980×1760
Engine Technical Specification:
– Brand: CCEC
– Engine Model: NTA855-G1A
– Cylinder NO.: 6 Cylinders in-line
– Prime Power(kW/HP): 261kW/345HP
– Standby Power(kW/HP): 291kW/396HP
– Rated Speed(RPM): 1500rmp
– Bore*Stroke(mm): 145×152
– Displacement(L): 14L
– Exhaust Temperature(℃): 468
– Lubricating Capacity(L): 34L
– Liquid Cooling Capacity(L): 63.8L
– Fuel Consumption(g/kW.h): 207 g/kW.h
– Oil Consumption(g/kW.h): 0.4 g/kW.h
– Aspiration Method: Turbocharged
– Starting System: Electrical start
– Cooling System: Water cooling
– Governor Type: Electrical Control
Alternator Technical Specification:
– Brand: HY
– Model: HY-G220
– Rated Capacity(kW/kVA): 220kW/275kVA
– Output Voltage: 400/230V
– Enclosure Degree: IP22
– Insulation Degree: H
– Connecting Type: 3PH star, 3PH-DELTA
Applications of Cummins NTA855-G1A Generators:
– Industrial power supply: Provide reliable power support for industrial facilities.
– Data center: Ensure continuous power supply to data centers to ensure data security and business continuity.
– Hospitals and medical facilities: Provide reliable backup power in emergencies to ensure the normal operation of medical equipment.
– Construction: Provide temporary power supply for construction sites.
– Mining and oil fields: Provide stable power support in remote areas and harsh environments.